Section 17. TROUBLESHOOTING GUIDE
SYSTEM
SYMPTOM POSSIBLE CAUSE REMEDY
1. Low Battery message on
keypad or battery trouble
LED lit.
1a. "Bat" or “System Low Bat”
1a. System battery is low or missing.
2. Nuisance or phantom alarm. 2a. Sensors not properly installed, wired, or
monitored.
2a. Check installation to see if in accor dance
with established procedure.
3. "AC POWER" light off. 3a. Interrupted AC power supply. 3a. Check transformer connection and Power
line circuit breaker.
4. “CHECK” and zone number
1–5 is displayed.
4a. Control has sensed an open circuit on one
or more zones
4a. Check the sensor or the loop wiring in
the affected zone. The system will not
display "System Normal" until this
condition is corrected (or the affected
zone is bypassed).
CONTROL
SYMPTOM POSSIBLE CAUSE REMEDY
2. Digital control message not
being received.
2a. Ademco 5110XM in FIRE WALK TEST
mode.
2b. Telephone connection not secure.
2c. Digital control malfunctioning.
2d. Telephone number in program needs
prefix or access code.
2e. Telephone call to central monitoring
station requires operator assistance.
2a. Remove from TEST mode.
2b. Check all connections.
2c. Check with a different Ademco 5110XM.
2d. Program prefix or access code into the
Ademco 5110XM.
2e. Ademco 5110XM system cannot work in
this situation.
3. Ademco 5110XM doesn't re-
spond to keystrokes on
keypad.
3a. "CC" or "MODEM COMM" displayed.
3b. "d1" or "System Busy" displayed.
3c. Keypad address setting incorrect.
3a. System is in communication with down-
loader at central station. Wait until
download session is finished.
3b. System has just been powered and is in
its one minute initialization. To bypass
this time, press '#' + '0'.
3c. Keypads must be set for address 31 (non-
addressable mode).
SMOKE DETECTOR
SYMPTOM POSSIBLE CAUSE REMEDY
1. Detector alarms, no ap-
parent reason.
1a. Dust, dirt in sensing chamber.
1b. Improper location.
1c. Unit malfunctioning.
1a. Clean unit's sensing chamber with
vacuum cleaner per unit's instructions.
1b. See unit's instructions for locations to
avoid. Relocate as necessary.
1c. Replace detector.