– 30 –
2. Use a wire nut (not supplied) to splice this earth ground wire to the green
flying lead located inside of and bonded to the transformer enclosure. Push
the mated wires into the enclosure.
3. Connect the green flying lead which emerges from the top of the transformer
enclosure to the 5110XM's earth ground terminal (Terminal 8).
4. Replace the transformer enclosure cover after wiring is complete.
Powering Up the System
Apply AC power to the control. Following power-up, Busy-Standby (alpha
keypads) or NOT READY (fixed-word keypads) will be displayed.
After approximately 1 minute, the initial displays will revert to SYSTEM
NORMAL for alpha keypads, or AC for fixed-word keypads (if there are no
faulted zones).
To bypass this delay, press: [#] + [0].
Connecting The Back-Up Battery
In the event of an AC power loss, the control must be supported by a back-up,
rechargeable 12V, 7AH min/14AH max sealed lead acid (gel cell type) battery.
The battery's capacity must be sized to provide 24 hours (UL Central Station
Fire) or 60 hours (UL Remote Station Fire) of standby time followed by 5
minutes of alarm time. Use the steps below to calculate the required battery
capacity.
Calculating the Battery Size Needed
Use the worksheets below to determine the total standby and alarm loads and
the required battery capacity. Then select a battery having a capacity greater
than or equal to the calculated capacity.
Komentarze do niniejszej Instrukcji