– 20–
Programming Hard-Wired Zones
1. With at least one Alpha keypad (6139 or 6139R) connected to the keypad
terminals on the control, power up the system temporarily.
2. Enter the programming mode by keying the following on the Alpha keypad:
Master code (5 1 1 0) + 8 0.
3. Press
*56
. Note that this is an interactive programming mode. You will
use it to program zone numbers, zone types, and alarm report codes.
Enter Zn Num.
(00 = Quit) 01
Zone Number
↑
Upon entering
*56
mode, this prompt will be
displayed. Enter the first zone number that
you wish to program (or [0][0] to exit zone
programming). If you are starting with zone 2,
enter “02”. Press
*
to continue.
Typical summary display
Zn ZT RC
02 09 00
A summary display will appear, showing the
present status of that zone's programming.
Zn = zone number;
ZT = zone type;
RC = report code for that zone;
Values displayed are currently programmed
values.
If the zone is programmed satisfactorily, press
[#] to back up one step and enter the next zone
number, if desired.
If you want to change a zone’s programming,
press [*]. A prompt for Zone Type will appear.
↓
Zone Number
02 Zone Type
Fire 09
Zone Type
↑
Each zone must be assigned a zone type, which
defines the way in which the system responds
to faults in that zone. A detailed explanation of
each zone type is provided in “Response Type
Definitions” in the ZONE RESPONSE TYPE
DEFINITIONS section.
Enter the desired zone type code, as listed
below.
00 = Zone Not Used
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire (NO verification.)
16 = Fire (Verification)*
17 = Fire Waterflow
18. = Fire Supervisory
19. = 24 Hour Trouble
*The “verification” feature is only active when zone
type 16 is assigned to 2-wire smokes on zone 5 only or
for 4-wire smokes on any zone that is powered from the
Aux Power Relay.
Note: When used as a slave DACT for a listed FACP,
use response type 09 for zones wired to FACP fire
alarm, type 18 for supervisory, and type 19 for trouble
contacts.
When the display shows the zone type you want,
press [*] to continue.
You must enter “00” as the zone type for any hard-wired zones that are not
used.