5110XMN8026 4/96Installation Instructions • Installation Instructions • Installation InstructionsControl/Communicator

Strona 2 - TABLE OF CONTENTS

– 10–CABINET DOOR BOTTOMRETAINERCLIPRETAINER CLIP(NOTE POSITION)RETAINERSLOTSLOCKEDUNLOCKEDFigure 1. Installing The Cabinet Lock1. Remove the cabinet

Strona 3 - LIST OF FIGURES

– 11–1. Make sure that the mounting screws are tight. This insures that there is agood ground connection between the PC board and the cabinet.2. Dress

Strona 4 - HOW TO USE THIS MANUAL

– 12–The system will not switch to the backup dialer unless it detects a fault (lessthan 2 volts) on the main telephone line. This means that if a re

Strona 5

– 13– Section 3. INSTALLING REMOTE KEYPADSThis section provides the following information:• A list of keypads that may be used• Instructions for w

Strona 6

– 14– KEYPADYELLOWREDGREENKEYPAD CONNECTOR CABLE (supplied with keypads)BLACK17181920ControlTerminalsFigure 3: Keypad Connections To The Control Boar

Strona 7

– 15– Section 4. MECHANICS OF PROGRAMMINGThis section provides the following information:• How to enter and exit the programming mode• How to pro

Strona 8

– 16–desired data, then press [*] plus the next data field number to beprogrammed.4. If you try to enter a non-existent field, the keypad will display

Strona 9

– 17– Section 5. BASIC HARD-WIRED ZONES 1-5This section provides the following information:• General information about hardwired zones• Installing 2

Strona 10

– 18–Remove 2000 ohm EOL resistor if connected across the zone terminals, andconnect it across the loop wires at the last detector.3. To supervise pow

Strona 11

– 19–1516ZONE 1SMOKE(+)(-)2 WIRE SMOKEDETECTOR2KEOLRZONE 5Figure 5: 2-Wire Smoke Detector Connected to Zone 5COMPATIBLE 2-WIRE SMOKE DETECTORSDetector

Strona 12

TABLE OF CONTENTSSection 1: GENERAL DESCRIPTION ... 6Basic Hardwired...

Strona 13

– 20–Programming Hard-Wired Zones1. With at least one Alpha keypad (6139 or 6139R) connected to the keypadterminals on the control, power up the syste

Strona 14

– 21 –02 Report Code1st 03 2nd 12 3CThe report code consists of 2 hexadecimal digits,each in turn consisting of 2 numerical digits. Forexample, for

Strona 15

– 22 –If the warning buzzer is sounding or if the following is displayed on anoptional Alpha keypad,Check xx Zone xxpress the silence/reset button (l

Strona 16 - Typical prompt displayed

– 23 – Section 6. SYSTEM ZONESThis section provides the following information:• General information about system zones• System zone assignments

Strona 17

– 24 – Section 7. ALARM INDICATING DEVICESThis section provides the following information:• General information about the bell circuit output• Co

Strona 18 - Four-Wire Detector Circuit

– 25 –Sounder Connections Make connections to alarm output terminals 3 (+) and 4(-) (see Figure 6).To supervise the bell wiring, do the following:• Co

Strona 19 - DETECTOR

– 26 –7. Press *86 (Zones 10-12, 95, and 96 Bell / Aux. Relay Activation) 0 Enter [0] for NO ALARM ACTIVATION (*always enter

Strona 20 - Zone Number

– 27 –Section 8: AUXILIARY RELAY CONNECTIONSThis section provides the following information:• General information about the auxiliary relay• Wiring t

Strona 21 - Typical summary display

– 28 –Programming the Auxiliary RelayThe auxiliary relay may be programmed for one of the following options:• Trouble/Supervisory Activation• Alarm Ac

Strona 22

– 29 – Section 9. FINAL POWER UPThis section provides the following information:• Connecting the AC transformer• Making earth ground connection

Strona 23 - Section 6. SYSTEM ZONES

– 3–Assigning Zone Descriptors ... 34Entering Zone Descriptors

Strona 24

– 30 –2. Use a wire nut (not supplied) to splice this earth ground wire to the greenflying lead located inside of and bonded to the transformer enclos

Strona 25

– 31 –TOTAL STANDBY/ALARM LOAD WORKSHEETSTo calculate the total current for the Aux. power, bell & aux. relay outputs, multiply each device's

Strona 26 - 0

– 32 –4) Enter the calculatedsubtotals of all listedoutputs then add to getcombined current.COMBINED AUX. POWER, BELL AND RELAY OUTPUT Total CurrentSt

Strona 27 - HARDWIRED ZONE (ZN 1-5)

– 33 –3. If two batteries are required, connect them in parallel using the dualbattery harness. Both batteries should be mounted as shown in the figur

Strona 28

– 34 –Section 10.ALPHA DESCRIPTOR PROGRAMMINGThis section provides instructions for programming alpha descriptors, which is recommendedfor systems usi

Strona 29

– 35 –4. Press “0” (No).* The system will thenautomatically display the descriptor forzone 1. * The procedure for adding custom words tothe built-in

Strona 30

– 36 –S ZN 01 BACKDOOR A+Flashing Cursor if “6” ispressed (system ready fornext word). 9. Press “6” to accept the selected word. Note: If these

Strona 31 - = Standby Alarm

– 37 –4. For selection of the next word (e.g., DOOR), repeat step 3, as follows.Press key [3] until the first letter of the next word appears (e.g., &

Strona 32

– 38 –ALPHA VOCABULARY LIST(For Entering Zone Descriptors)000 (Word Space)A001 AIR002 ALARM003 ALCOVE004 ALLEY005 AMBUSH006 ANTENNA007 AREA008 APARTME

Strona 33

– 39 –CHARACTER (ASCII) CHART(For Adding Custom Words)32 (space)33 !34 "35 #36 $37 %38 &39 '40 (41 )42 *43 +44 ,45 –46 .47 /48 049 151 3

Strona 34 - ALPHA DESCRIPTOR PROGRAMMING

– 4–HOW TO USE THIS MANUALThis manual is written to accommodate both the new and the experienced installer ofAdemco products. A general description of

Strona 35 - S ZN 01 BACK

– 40 – Section 11. SYSTEM COMMUNICATIONThis section provides the following information:• General information about system communication• An explanati

Strona 36

– 41 –The following describes each format in greater detail.3+1 and 4+1 Standard Formats Comprise a 3- (or 4-) digit subscriber number and a single di

Strona 37

– 42 –Where:SSS or SSSS = Subscriber IDA = Alarm Code–1st digit Gg = Test Code (1st & 2nd digits)Z = Typically Zone Number*–2nd digit GOGO2= Off

Strona 38 - ALPHA VOCABULARY LIST

–43–Programming Communication Options To program communications options, do the following:1. With at least one alpha keypad (6139 or 6139R) connected

Strona 39 - CHARACTER (ASCII) CHART

–44–Press *47 SPLIT/DUAL REPORTING Enter 0 to disable (Backup report only). This is the default.TO PRIMARY TO SECONDARY 1 = Alarms, Restore Oth

Strona 40

–45–This will be sent when the supervisory condition is restored.Press *60 TROUBLE REPORT CODE | This will be sent if a zone goes into trouble.Pr

Strona 41

–46–Press *95 RING DETECTION COUNT FOR DOWNLOADING Refer to the chart below and program this field accordingly.AnsweringMachine Downloading Field

Strona 42

–47– Section 12.ZONE RESPONSE TYPE DEFINITIONSThis section provides the following information:• General information about zone response types• Zone

Strona 43

–48–Type 17Fire Waterflow Alarm• Provides a fire alarm when zone is shorted for longer than the timeprogrammed in field *78 delay time setting. The c

Strona 44

–49– Section 13. DATA FIELD DESCRIPTIONSDescription of System Data FieldsTHE BLANK PROGRAMMING FORM INCLUDED WITH THIS MANUAL SHOULD BE USED TOREC

Strona 45 - FIRE W/T FIRE W/T OFF

– 5–CONVENTIONS USED IN THIS MANUALMAIN SECTION TITLES ARE SHOWN IN REVERSE TYPEBefore you begin using this manual, it is important that you understan

Strona 46

–50–*31AUXILIARY RELAY TIMEOUT This field determines whether the auxiliary relay will shut off aftertime allotted, or continue until manually t

Strona 47 - Section 12

–51–*46 REPORT FORMAT (* applies to BOTH primary and secondary numbers) Determines which format is to be used to report to t

Strona 48

–52–↓ Zone Number01 Zone TypeFire 09Zone Type ↑Zone Type (ZT): Each zone must be assigned to a zone type, whichdefines the way in

Strona 49

–53–01 Zone TypeNot Used 0001 Delete Zone?1 = Yes 0 = No3. To either temporarily or permanently remove a zone from the system,go into programming mo

Strona 50

–54–*64 NORMAL TEST REPORT CODE | This is sent periodically to test that the communicator and phone linesare operational (frequency of repo

Strona 51 - Zone 01 entered ↑

–55–*85 ZONES 1-7 BELL & AUX. RELAY ACTIVATION 1 2 3 4

Strona 52

–56– Section 14. REMOTE PROGRAMMING AND CONTROL (DOWNLOADING)General InformationThe Ademco 5110XM can be remotely programmed from an IBM compat

Strona 53

–57–Central Station Initiated:1. Enter program mode by entering Master code (5110) + 8 0.2. Program the download phone number in field *94.3. Program

Strona 54

–58– Section 15. SYSTEM OPERATIONThis section provides the following information:• User codes• Keypad functions• Emergency keysUser Codes* User cod

Strona 55

–59–Keypad Functions The keypad, if used, allows the user to silence alarm and trouble sounders andperform other system functions, such as bypassing z

Strona 56 - CONTROL (DOWNLOADING)

– 6– Section 1. GENERAL DESCRIPTIONThe Ademco 5110XM is a UL Listed, microprocessor-based fire alarmcontrol/communicator that supports 5 style

Strona 57

–60– Section 16. TESTING THE SYSTEMTest Procedure After installation is completed, the 5110XM System should be carefully tested, asfollows:1. With

Strona 58

–61–Dialer TestThe 5110XM may be programmed to send periodic test reports ranging fromevery 24 hours, weekly, or monthly, as determined in field *49.

Strona 59

–62– Section 17. TROUBLESHOOTING GUIDESYSTEMSYMPTOM POSSIBLE CAUSE REMEDY1. Low Battery message onkeypad or battery troubleLED lit.1a. "Bat&qu

Strona 60

–63–CONTACTING TECHNICAL SUPPORTPLEASE,Before you call Technical Support, be sure you:• READ THE INSTRUCTIONS!• Be on site with all documentation (man

Strona 61

–64– Section 18. SPECIFICATIONS & ACCESSORIESSpecifications ––––––––––––––––––––––––––––––––––––––––––––––––––––CONTROL 1. Physical: 12-1/2&q

Strona 62 - SMOKE DETECTOR

–65–AGENCY LISTINGSFire:• UL864-NFPA 72 Central Station and Remote Station DACT and local,central station and remote station control.• FM pending• CS

Strona 63 - CONTACTING TECHNICAL SUPPORT

–66–Accessories (Compatible Devices) –––––––––––––––––––––––––––––––––––SoundersSystem Sensor PA400B(beige)/PA400R (red)Indoor piezo sounder (red or b

Strona 64 - Specifications

–67–REGULATORY AGENCY STATEMENTSThe 5110XM may be used as a slave DACT providing central or remote station service for a central orremote station list

Strona 65

–68–FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENTThis equipment complies with Part 68 of the FCC rules. On the front cover of this equipme

Strona 66

–69–WARNINGTHE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced design security system, it does not offer guaranteed protection agains

Strona 67 - REGULATORY AGENCY STATEMENTS

– 7–Bell OutputProvides one 12VDC (nominal), 1 AMP output, which may be configured forStyle Y (for further explanation of style Y, refer to NFPA 72 Na

Strona 68

–70–ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiariesand affiliates ("

Strona 69

–71–INDEX1100, 19,.661400, 19, 661412, 19, 661451, 19, 661451DH, 19, 662100, 19, 662100T 19, 662112/24T, 19, 6624-hour Audible Alarm, 4724-hour Silent

Strona 70 - ADEMCO LIMITED WARRANTY

–72–Default Descriptor , 35DEFAULT VALUES, 55Description of System Data Fields, 49Dialer Operation, 11DIALER PROGRAMMING, 50Dialer Test, 61DOWNLOAD IN

Strona 71

–73–SESCOA/RADIONICS SELECT, 44, 51Silence/Reset key, 19, 22Silencing Sounders, 59sirens, 24Site Initiated Remote Programming, 56slave DACT, 6SMARTMOD

Strona 72

–74–NOTES

Strona 73

– 75–N.C.N.C.N.O.N.O.2K2KN.C.N.C.N.O.N.O.2K2KN.C.N.O.2K2-WIRE SMOKE DETECTOR LOOPREMOTE KEYPAD.OPTIONAL FORSLAVE DACTINSTALLATIONS.REQUIRED FORSTAND A

Strona 74

N8026 4/96ALARM DEVICE MANUFACTURING CO.A DIVISION OF PITTWAY CORPORATION165 Eileen Way, Syosset, New York 11791Copyright © 1995 PITTWAY CORPORATION

Strona 75 - 5110XM SUMMARY OF CONNECTIONS

– 8–Back-Up BatteryUses a rechargable 12VDC, 7AH/14AH maximum lead acid (gel cell) battery forback-up power (dual battery cable supplied)Agency Listin

Strona 76 - N8026 4/96

– 9– Section 2. INSTALLING THE CONTROLThis section provides instructions for getting the system up and running quickly, as well asdetailed instruction